AMC16-DETT Base station Multi-Circuits DC Energy Meter

Short Description:

● Rated voltage/currentdefault six-way Hall element, total measurement 200A/5V

● Accuracy range: 1%In≤I≤10%In error±2.5%; I>10%In error±2%

● Hall power supply: +12V/100mV, -12V/50mA

● Voltage range: -40V~-60VDC

● Communication: RS485 interface (protocol YD/T1363.3-2014)

● Installation: 35mm rail installation

● Product Dimension: 89.7*87.8*52mm


Product Detail

parameters

Overview

Base station dedicated DC energy meter AMC16(L)-DETT is specially designed for base stations where have sharing requirements, and switch power supply is without the function of sub-user metering. The meter could measure 6 circuits DC energy, and supply working current to the matched hall sensors. Meanwhile, it can realize zero drift calibration by upper computer software. have the functions of telemetering,teleindication,teleadjusting, metering at real time, energy quality abnormal alarm, data storage and processing, data interaction. This meter can measure  DC power consumption of three operators, providing detail datas for base station.

1

Features

2

Products Show

3
4
5

Dimension and wiring

6
7

Networking Scheme

8

  • Previous:
  • Next:

  • Technical parameters

    Technical parameter

    Index

      

     

     

     

           input

    DC rated voltage

    1 channel: -48VDC

    DC current

    6 channels hall sensors output is 5V,current ratio can be set  according to the actual ratio

    Commercial power

    monitoring

    1 channel: 0-5VDC

     

    Overload capacity

    Voltage:1.2times continued,2 times continued 1s;Current: 1.2 times continued,10 times continued 1s.
    Accuracy (superposition hall sensors) 1%In≤I≤10%In error±2.5%; I>10%In error±2%
     Measurement resolution Voltage output accuracy 0.01V;    current output accuracy 0.01A;power output accuracy 0.01kw; energy output accuracy 0.01kwh.
      

     

     

     

     

     

     

     

    functions

     Basic function Monitor device system time, total voltage, output total current, power, energy, each channel voltage, current, power, energy; LED indicator display;485 communication.
      

     

     

    Metering function

    Start current: under rated voltage, when the load current value of the meter doesn’t exceed 1% of the max. current, the meter starts.Shunt running current: when there is no current in the current circuit of the meter, and 85%-125%of the rated voltage is applied on the voltage circuit, the calculator shall not have more than one digital change.
      

    Alarm function

    DC voltage output low alarm,DC voltage output high alarm,one power down alarm, module voltage loss alarm, metering branch error alarm, internal program error alarm, clock error alarm,memory failure alarm, AC input power failure alarm
     Timing function support broadcast timing, could remote timing to the meter through RS485 communication.
     Communication

    Single channel RS485, baudrate 9600bps, can be set to 1200BPS, 2400bps, 4800bps.

    Communication protocol: standard or custmized

     

     

     

      Hall sensor powersupply  Power supply output:+12V/100mA, -12V/50mA
    Clock accuracy ≤0.5S/d(23℃), ≤1S/d(-20℃-60℃),
    Auxiliary powersupply Voltage range -40V~-60VDC
    Power consumption Whole device≤2W( no hall power supply output)
     

    Storage

    It has the storage function of historical power data and historicalalarm information, and the memory is 2MB
    Insulation resistance ≥40MΩ
     environment Temperature Working : -20℃~+60℃; storage:-40℃~+70℃
    Humidity ≤98% no condensation, no corrosive gas place

    Altitude

    ≤4000m

    Protection level

    IP20
     Material flame retardent Terminal glow wire temperature 960℃±10℃ ,shell glow wiretemperature 650℃±15℃

    installation

    Standard 35mm din rail
     Lightning protection Voltage input(differential mode)  Peak value 5kA