DJSF1352-RN rail-mounted DC power meter

Short Description:

● Measurement: kWh, kVarh, Power, Current, Voltage and etc

● Current Rating: Shunt 0-75mV; Hall sensor 0-20mA,4-20mA,0-5 V,0-10V

 Voltage Rating: 0~1000V DC

● Application: DC Battery; Charging Pile; Solar PV and etc

● Communication: DL/T645-2007 Protocol, MODBUS-RTU Protocol

 Power Supply: 85~265V AC/DC; 24V(±10%) DC; 48V(±10%) DC

 Pulse Input: One Second pulse output, one electric energy pulse output

● Display: 8 Digital Segment type LCD

● Dimension: 72*71*87.8mm (L*W*H)

● Installation: 35mm DIN Rail

● Standard&Certificate: CE


Product Detail

parameter

General

DJSF1352-RN rail-mounted DC power meter with double DC input channels, designed for telecommunications base stations, DC charging piles, solar photovoltaic and other applications, this series of meters can measure the voltage, current, power and forward and reverse energy and so on in the DC system.

1

 SOE Event Record

 Infrared Communication

 BI-Direction Active Power Measuring

 Multi-Tariff Function

 8 Digital LCD Display

 Maximum Voltage Output 1000V 

Product Size

2
3

Features

4

Application

5
6

Installation Image

7

  • Previous:
  • Next:

  •  Technical parameters

    Technical parameters

    Index

    Input

    Nominal value

    Voltage input range

    Current input

       

    DC 0-1000V

    See the physical wiring diagram

    Shunt0-75mV

    Hall sensor0-20mA4-20mA0-5V0-10V and so on.

           
     

    Overload

    1.2 times rated (continuous); 2 times rated/1 second;

     

    Power consumption

    Voltage: ≤0.2VA, current ≤0.1VA

    Accuracy class

    Class 1 or Class 0.5

    Function

    Display

    8-bit segment LCD screen (LCD)

     

    Communication Interface

    RS485two options

     

    Communication protocol

    Modbus-RTUDL/T 645-2007

     

    Switch

    Switch output

    2 Relay outputs, 2A/30VDC or 2A/250VAC
       

    Switch input

    2 dry contact inputs

     

    Pulse output

    A second pulse output, a energy pulse output

        See the SYS->PLUS display in the meter menu settings. For example: The meter displays 100, which is 100imp/kWH

    Power Supply

    Voltage range

    AC/DC 85-265V or DC24V(±10%) or DC48V(±10%)

     

    Power consumption

    3W

    Pulse constant

    Maximum power

     

    999.9W

    10000

    imp/kWh

    9.999kW

    1000

    imp/kWh

    99.99kW

    100

    imp/kWh

    999.9kW

    10

    imp/kWh

    9999kW

    1

    imp/kWh

    Maximum power = rated voltage * voltage ratio * current ratio * 1.2