Technical parameters
Technical parameters |
Indicators |
||
Input |
Grid |
Single-phase |
|
Frequency |
45~65Hz |
||
Voltage |
Rated voltage: AC 100V, 400V |
||
Overload: 1.2 times the rated voltage(continuous); 2 times the rated voltage lasting for 1 second |
|||
Power consumption: less then 0.2VA |
|||
Current |
Rated current: 10A,20A,40A,80A,120A,200A etc. (for details see product specifications) |
||
Overload: 1.2 times the rated current(continuous);10 times the rated current lasting for 1 second |
|||
Power consumption: less then 0.2VA |
|||
Output |
Communication |
RS485 interface, Modbus-RTU |
|
Display |
LCD |
||
Measurement precision |
Voltage: 0.2 level, current, power Active energy: 0.5 level,0.01Hz frequency, Reactive energy: 1 level |
||
Power supply |
AC85~265V or DC100~350V; power consumption ≤10VA |
||
Safety |
Power frequency withstand voltage |
AC2kV 1 min between power supply // current input//voltage input and communication AC2kV 1 min between each pair of combinations among power supply, urrent input and voltage input. |
|
Insulating resistor |
Input,output terminal to housing >100MΩ |
||
Environment |